The parameter information is for reference only. The specific situation shall be subject to the actual equipment nameplate and product manualGet Details
(1) Three sets of clean room purification air conditioning units (AHU1, AHU2, AHU3) for production lines:
Manufacturer: Shanghai Yiling Kaili Air Conditioning Equipment Co., Ltd. Tonghui Air Conditioning Equipment Factory
Main parameters: Rated air volume of 35000 m³ /h、 51000 m³ /h、72000 m³ /h. The cooling and heating capacities are 233.7 KW/168.8 KW, 301.7 KW/275.2 KW, and 411 KW/330.4 KW, respectively;
(2) Double head water-cooled screw chiller unit:
Manufacturer: Shanghai Yiling Kaili Air Conditioning Equipment Co., Ltd
Unit model: 30HXC250E; Cooling/heating capacity: 874 KW, cold water outlet temperature (cooling): 7 ℃; Cooling water inlet temperature (refrigeration): 30 ℃; Cold water/cooling water flow rate: 150 m³ /h 188 m³ /h. Refrigerant working fluid: R134a; Refrigerant capacity A/B/C: 117kg/75kg/-; Performance coefficient: 4.88
(3) 16 sets of air-cooled heat pump hot water units (4 sets of vortex air-cooled heat pump units)
Manufacturer: Shanghai Yiling Kaili Air Conditioning Equipment Co., Ltd
Main parameters: Factory codes: SRQBS1572, SRQBS1574, SRQBS1617, SRQBS1621; Unit model: 30RQ130BMS; Cooling/heating capacity: 130.0 KW/138.0 Kw; Cold water inlet temperature (heating): -; Hot water outlet temperature (heating): 45 ℃; Cooling water inlet temperature: -; Cold water outlet temperature (refrigeration): 7 ℃; Cold/hot water flow rate: -/24.0 m³ /h. Cold water/cooling water flow rate: 22.3 m³ /h /-; Refrigerant working fluid: R410a; Refrigerant capacity A/B/C: 17.0/17.0kg; Comprehensive performance coefficient: 3.34;
(4) Cooling Tower: Lingke
(5) 2 chilled water pumps
Manufacturer: Guangzhou Guangyi Pump Industry Co., Ltd
Main parameters: Model: GDD 150-32; Traffic: 200 m³ /h, Head: 32m; Speed: 1480 r/min; Power: 30KW; Efficiency: 79%
(6) Cooling water pump (2 units)
Manufacturer: Guangzhou Guangyi Pump Industry Co., Ltd